ATS Philosophy1) ATS will control VCB-1,2,3 and both DG set 1 and 22) When VCB-1 is OFF- The ATS should be ensured that supply is failure from electricity and both VCB-2 and 3 OFF Condition. Then it will give start command to both DG sets.3) Once both DG’s will reach to rated speed and voltage, then the both ACB will be closed immediately and then after 3 seconds any one of the breaker (VCB 2 or VCB-3 ) will be closed by dead base mode position and another one breaker (VCB 2 or VCB 3) will be closed within 3 seconds by synchronous controller. 4) When VCB-1 is ON- The ATS should be ensured that supply is available from electricity, it will immediately give stop command to both DG sets and VCB-2 and 3.