BILL NO. 4: MECHANICAL
Cluster of 2*12 Factory Units (900m2)
Item Description Unit
15 DIVISION 15- MECHANICAL WORKS
15.1 FIRE PROTECTION SYSTEM
Supplying, installing, aligning, testing and commissioning of the fire protection network, complete with pipes, fittings, test plugs, hangers & supports, excavation and backfilling, fresh clean water for hydro test and all other accessories required for completion of the system.
15.1 Supply and install UPVC Pipes and fittings, schedule 80, complete with supports,excavation and backfilling and all other accessories as per drawings.
15.1.1 6" Ø Lm
15.1.2 4" Ø Lm
15.1.3 21/2" Ø Lm
15.1.33 11/2" Ø Lm
15.1.4 Supply and install seamless carbon steel pipes and fittings, schedule 40, , ASTM A 53 complete with hangers & supports, painting and accessories.
15.1.5 6" Ø Lm
15.1.6 4" Ø Lm
15.1.7 21/2 Ø Lm
15.1.8 11/2" Ø Lm
15.1.9 Supply and install fire hose cabinet (FHC-1), complete with 30m long hose, nozzle, shut-off valve and fixing accessories. No.
15.1.10 Supply and install fire hose cabinet (FHC-2) with foam, complete with 30m long hose, nozzle, shut-off valve and fixing accessories. No.
15.1.9 Supply and install portable fire extinguisher (FE-1), chemical powder, type ABCE, 6kg capacity with mounting hook and accessories. No.
15.1.9.1 Supply and install portable fire extinguisher (FE-2),CO2, wheel type, 6kg capacity includes all accessories. No.
15.2.1 Supply and install OS&Y Gate valve complete with valve box
15.2.1.1 4" Ø No.
15.2.1.2 2.5" Ø No.
15.2.1.3 Supply and install Fire Alarm Check Valve (ACV) assembly, complete with accessories.
6" Ø No.
15.2.2 Supply and install Fire Hydrant with (valve box with gate valve) , complete with accessories. No.
15.2.3 Supply, install, test and commissioning a complete set of fire pumps - UL/FM comprising of main electric driven pump, diesel pump and jockey pump,split case type, complete with pipes, valves, gauges, switches, control panel, diesel day tank and necessary accessories to put the system in reliable operation. Set
15.2.3.1 Main Electric Driven Pump: 500gpm, 8bar, 55hp 380v / 60hz
15.2.3.2 Diesel Driven Pump: 500gpm, 8bar, 60bhp
15.2.3.3 Jockey Electric Driven Pump: 50gpm, 8bar, 6hp
15.2.4 Supply and install Fire Department Connection(FDC) 4" with check valve as per specs and drawings. Set
15.3 WATER SUPPLY SYSTEM
15.3.1 Supply and installation of UPVC pipes, schedule80for cold water supply piping system, complete with fittings and accessories.
15.3.1.1 4" Ø Lm
15.3.1.2 3" Ø Lm
15.3.1.3 2" Ø Lm
15.3.1.4 21/2" Ø Lm
15.3.1.5 11/2" Ø Lm
15.3.1.6 11/4" Ø Lm
15.3.1.7 1" Ø Lm
15.3.1.8 1/2" Ø Lm
15.3.1.7 3/4" Ø Lm
15.3.2 Supply and install valve box with gate valve, complete with accessories.
15.3.2.1 21/2" Ø No.
15.3.2.2 11/2" Ø No.
15.3.2.3 1" Ø No.
15.3.2.4 Gate Valve (GV)
15.3.2.4.1 21/2" Ø Nos.
15.3.2.4.2 11/2" Ø Nos.
15.3.2.5 Supply and installation of CPVC pipes, schedule 80 for hot water supply piping system, complete with fittings and accessories.
15.3.2.5.1 1" Ø Lm
15.3.2.5.2 3/4" Ø Lm
15.3.2.5.3 1/2" Ø Nos.
15.3.2.5.4 Gate Valve (GV)
11/2" Ø Nos.
15.3.2.5.5 Supply and installation of Water hammer arrestor complete according to specification including all other necessary accessories for each toilet room Nos.
15.3.2.6 Mixer for the lavatory / wash basin , single lever arm with accessories Sets
15.3.2.7 Perenial spray (PS) for each water closet Sets
15.3.2.8 Hose Bibb, 3/4" Nos.
15..3.2.9 Supply and install electric water heater(EWH) vertival type, 50 Liters, below ceiling, complete with mounting bracet, angle valves and all other accessories. Nos.
15.3.2.10 Supply and install electric water heater(EWH) vertival type, 30 Liters, below ceiling, complete with mounting bracet, angle valves and all other accessories. Nos.
15.3.3 supply, install Booster pump set, 2 pumps , 2 duty- 1 standby, 5hp,100 gpm,.4 Head bar, 220v-1P-60hz, complete with valves, control panel, pressure switch, gauges, pipe headers, expansion tank complete with testing and commisioning and all other required accessories to put the system in operation. Set
15.4 SEWER AND DRAINAGE SYSTEM
15.4.1 Supply and installation of Submersible pump set, 2 pumps , 1 duty- 1 standby, 1/2hp, 30 gpm.1 head bar, 220v-1P-60hz, complete with valves, control panel, pressure switch, gauges, pipe headers, . testing and commissioning and all other required accessories to put the system in operation. set
15.4.2 Supply and installation of uPVC pipes, schedule 40 for sewage ,drainage piping system and vent piping system,, complete with fittings and accessories.
15.4.2.1 8" Ø Lm
15.4.2.2 6" Ø Lm
15.4.2.3 4" Ø Lm
15.4.2.4 3" Ø Lm
15.4.2.5 2" Ø Lm
15.4.2.6 Floor drain (FD) with cover stainless steel 316 as per specs and drawings. Nos.
15.4.2.8 Supply and install Gully Traps with cover heavy duty and all other accessories as